Last updated:
Electrical Calculations
GorkyCAD performs all mandatory electrical calculations automatically as you design. Results update in real time — no manual recalculation needed.
Load Calculation
The Connected Load is calculated by summing the rated power of all consumers on a circuit. GorkyCAD applies demand factors according to the selected standard.
Per-circuit calculation:
- Installed power: sum of all consumer ratings (kW)
- Demand factor: configurable per circuit (0.5–1.0)
- Design current: P / (√3 × U × cos φ) for three-phase
Per-phase balancing: GorkyCAD distributes single-phase loads across phases and shows the imbalance percentage. A warning appears if imbalance exceeds 15%.
Voltage Drop
Voltage drop is calculated for every circuit using the formula:
ΔU% = (ρ × L × I × 100) / (S × U)
Where:
- ρ — conductor resistivity (copper: 0.0175 Ω·mm²/m, aluminum: 0.028 Ω·mm²/m)
- L — one-way cable length (m)
- I — design current (A)
- S — conductor cross-section (mm²)
- U — nominal voltage (230V phase, 400V line)
Limits per standard:
- IEC 60364-5-52: 3% for lighting, 5% for other loads
- IS 732 (India): 3% lighting, 5% power
- ГОСТ Р 50571.5.52: 3% освещение, 5% прочие
If voltage drop exceeds the limit, GorkyCAD highlights the circuit in red and suggests a larger cross-section.
Short-Circuit Current
GorkyCAD calculates:
- Ik” max — maximum short-circuit current at the busbar (for breaker breaking capacity)
- Ik min — minimum short-circuit current at the end of the line (for tripping time verification)
Calculation follows IEC 60909 / ГОСТ 28249.
Required inputs:
- Transformer power (kVA) and impedance voltage Uk%
- Cable length, cross-section, and material
- Busbar length and configuration (for 3D cabinets)
Protection Device Selectivity
For series-connected circuit breakers, GorkyCAD checks:
- Overload selectivity — upstream breaker must not trip before downstream
- Short-circuit selectivity — based on let-through energy I²t
- Time-current curves — plotted for visual verification
The selectivity report shows PASS/FAIL for each pair with detailed reasoning.
Thermal Check
For distribution boards modeled in 3D:
- Total heat dissipation of all devices (W)
- Cabinet volume and ventilation type
- Temperature rise °C
GorkyCAD warns if the internal temperature exceeds 40°C (IP54 enclosure) or 35°C (IP65).
Reports
All calculations are included in the Full Project PDF export:
- Load schedule — per-circuit and total
- Voltage drop table — every circuit
- Short-circuit currents — at busbar and endpoints
- Selectivity matrix
- Thermal report for 3D cabinets
Tips
- Set the supply transformer parameters in Project Settings before starting
- Verify demand factors — defaults are conservative
- For industrial projects, enable motor starting current analysis