Clause-by-clause review of PUE chapter 7.1 (7th ed.): intakes, flat boards, cable sections, 30 mA and 10 mA RCDs, sockets, installation heights, fire-protection RCD.
| Document | PUE 7, Section 7.1 Residential and public buildings |
| Edition | 2003 (ПУЭ-7, гл. 7.1) |
| Status | Current |
| Issued by | Ministry of Energy of Russia |
| Applies to | Electrical installations of residential and public buildings |
| № | Chapter / section |
|---|---|
| 7.1.1–7.1.15 | Scope, general requirements |
| 7.1.16–7.1.27 | Intakes, metering |
| 7.1.28–7.1.35 | Distribution and group boards |
| 7.1.36–7.1.46 | Wiring, cables, sections |
| 7.1.47–7.1.66 | Protection, apparatus, luminaires |
| 7.1.67–7.1.78 | Earthing, sockets, switches |
| 7.1.79–7.1.86 | RCDs and differential protection |
| 7.1.87–7.1.92 | Flat boards, safety |
7.1.1 Applies to residential, public, administrative and utility buildings.
7.1.14 Normal lighting mandatory; emergency/escape lighting per building codes.
7.1.22 Intake device (VU/VRU) with protection and control apparatus at the building entry.
7.1.26 Every intake: overcurrent protection + switching device.
7.1.28 Group boards outside flats (stairwells) or in flat hallways when suitable.
7.1.31 Risers in non-combustible shafts; protective devices per group in flat boards.
7.1.33 Flat board: intake protection, meter, group protection.
7.1.36 Copper only: ≥ 1.5 mm² lighting, ≥ 2.5 mm² sockets; aluminium not allowed in new residential wiring.
7.1.44 Socket groups 2.5 mm² — breaker ≤ 16 A.
7.1.50 Switches at 0.8–1.7 m by the door handle.
7.1.59 Bathroom luminaires IP44+ in zones 1–2.
7.1.68 All sockets in living rooms/kitchens: earthing contact to PE.
7.1.71 Socket height 0.3–0.9 m by convenience.
7.1.72 Kitchen: ≥ 4 sockets (excluding the hob).
7.1.79 Socket circuits: 30 mA RCD.
7.1.81 Bathrooms/showers: 10 mA RCD.
7.1.84 Fire protection at the intake: 100–300 mA selective RCD.
7.1.88 Separate PE and N busbars, labeled.
Chapter 7.1 is the electrician's "bible": grounded sockets (7.1.68), 30 mA RCDs (7.1.79), 10 mA in bathrooms (7.1.81), fire RCD 100–300 mA (7.1.84), copper 1.5/2.5 mm² (7.1.36).