PUE 7, Section 7.1 Residential and public buildings — clause by clause

Clause-by-clause review of PUE chapter 7.1 (7th ed.): intakes, flat boards, cable sections, 30 mA and 10 mA RCDs, sockets, installation heights, fire-protection RCD.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentPUE 7, Section 7.1 Residential and public buildings
Edition2003 (ПУЭ-7, гл. 7.1)
StatusCurrent
Issued byMinistry of Energy of Russia
Applies toElectrical installations of residential and public buildings

Document structure

№Chapter / section
7.1.1–7.1.15Scope, general requirements
7.1.16–7.1.27Intakes, metering
7.1.28–7.1.35Distribution and group boards
7.1.36–7.1.46Wiring, cables, sections
7.1.47–7.1.66Protection, apparatus, luminaires
7.1.67–7.1.78Earthing, sockets, switches
7.1.79–7.1.86RCDs and differential protection
7.1.87–7.1.92Flat boards, safety
PUE 7, Section 1PUE 7, Section 7PUE 7, Chapter 2PUE 7, Chapter 3PUE 7, Section 1PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 1PUE 7, Section 6 LightingSP 256PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 2PUE 7, Chapter 4PUE 7, Chapter 7PUE 7, Chapter 7GOST R 50571 Building electrical installations (Russian IEC 60364)PUE 7, Chapter 2PUE 7, Chapter 7SP 158PUE 7, Chapters 2SP 76GOST R 50571Japan: electrical rules (JIS, 100 V)

General (7.1.1–7.1.15)

7.1.1 Applies to residential, public, administrative and utility buildings.

7.1.14 Normal lighting mandatory; emergency/escape lighting per building codes.

Intakes and metering (7.1.16–7.1.27)

7.1.22 Intake device (VU/VRU) with protection and control apparatus at the building entry.

7.1.26 Every intake: overcurrent protection + switching device.

7.1.28 Group boards outside flats (stairwells) or in flat hallways when suitable.

Boards (7.1.28–7.1.35)

7.1.31 Risers in non-combustible shafts; protective devices per group in flat boards.

7.1.33 Flat board: intake protection, meter, group protection.

Wiring (7.1.36–7.1.46)

7.1.36 Copper only: ≥ 1.5 mm² lighting, ≥ 2.5 mm² sockets; aluminium not allowed in new residential wiring.

7.1.44 Socket groups 2.5 mm² — breaker ≤ 16 A.

Lighting (7.1.47–7.1.66)

7.1.50 Switches at 0.8–1.7 m by the door handle.

7.1.59 Bathroom luminaires IP44+ in zones 1–2.

Sockets (7.1.67–7.1.78)

7.1.68 All sockets in living rooms/kitchens: earthing contact to PE.

7.1.71 Socket height 0.3–0.9 m by convenience.

7.1.72 Kitchen: ≥ 4 sockets (excluding the hob).

RCDs (7.1.79–7.1.86)

7.1.79 Socket circuits: 30 mA RCD.

7.1.81 Bathrooms/showers: 10 mA RCD.

7.1.84 Fire protection at the intake: 100–300 mA selective RCD.

Flat boards (7.1.87–7.1.92)

7.1.88 Separate PE and N busbars, labeled.

Practical takeaways

Chapter 7.1 is the electrician's "bible": grounded sockets (7.1.68), 30 mA RCDs (7.1.79), 10 mA in bathrooms (7.1.81), fire RCD 100–300 mA (7.1.84), copper 1.5/2.5 mm² (7.1.36).