PUE 7, Section 1.7 Earthing and safety measures — clause by clause

Clause-by-clause review of PUE chapter 1.7 (7th ed.): TN-C/TN-S/TN-C-S/TT/IT earthing, direct and indirect contact protection, 30 mA RCDs, protective conductors, bonding. Clause numbers included.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentPUE 7, Section 1.7 Earthing and safety measures
Edition2002 (ПУЭ-7, гл. 1.7)
StatusCurrent
Issued byMinistry of Energy of Russia (2002–2003)
Applies toAll installations up to and above 1 kV: earthing and electrical safety measures

Document structure

№Chapter / section
1.7.1–1.7.15Scope, terms, earthing systems
1.7.16–1.7.31Protection against direct contact
1.7.32–1.7.49Protection against indirect contact
1.7.50–1.7.67Earthing arrangements
1.7.68–1.7.87Protective conductors, RCDs
1.7.88–1.7.105Equipotential bonding
1.7.106–1.7.118Inspection and maintenance
1.7.119–1.7.176Requirements for residential, public buildings and outdoor installations
PUE 7, Section 1PUE 7, Section 7PUE 7, Chapter 2PUE 7, Chapter 3PUE 7, Section 1PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 1PUE 7, Section 6 LightingSP 256PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 2PUE 7, Chapter 4PUE 7, Chapter 7PUE 7, Chapter 7GOST R 50571 Building electrical installations (Russian IEC 60364)PUE 7, Chapter 2PUE 7, Chapter 7SP 158PUE 7, Chapters 2SP 76GOST R 50571Japan: electrical rules (JIS, 100 V)

Earthing systems (1.7.3–1.7.15)

1.7.3 TN-C: combined neutral and protective conductor (PEN) throughout.

1.7.4 TN-S: separate N and PE throughout.

1.7.5 TN-C-S: PEN combined up to the intake, then split into PE and N — standard for new Russian buildings.

1.7.6 TT: neutral earthed, exposed parts earthed separately.

1.7.7 IT: neutral isolated (or earthed via high impedance), exposed parts earthed separately.

Direct contact protection (1.7.16–1.7.31)

1.7.31 Additional protection: RCD ≤ 30 mA.

Indirect contact protection (1.7.32–1.7.49)

1.7.36 Disconnection times (table 1.7.1): 0.4 s at 380/220 V, 0.2 s at 660/380 V.

1.7.45 TT: RCD-based protection, RA×Ia ≤ 50 V.

Earthing arrangements (1.7.50–1.7.67)

1.7.51 Earth resistance ≤ 4 Ω in TN systems (10 Ω below 100 kVA).

1.7.63 Underground earthing conductors: copper ≥ 10 mm², aluminium 16 mm², steel 75 mm².

Protective conductors and RCDs (1.7.68–1.7.87)

1.7.76/79 Exposed parts to PE; PE separate from N after the PEN split.

1.7.87 Residential group circuits: RCD ≤ 30 mA.

Equipotential bonding (1.7.88–1.7.105)

1.7.91 Main bonding in every building: pipes, steelwork, PE, lightning.

1.7.92 Supplementary bonding in bathrooms, saunas, wet rooms.

1.7.99–1.7.101 Bonding conductor sizes: main — ≥ half of the largest PE (6–25 mm² copper); supplementary per table 1.7.5.

Residential and public buildings (1.7.119–1.7.135)

1.7.120 No water/gas pipes, cable sheaths or rebar as PE.

1.7.123 Socket earthing contact must connect to PE.

1.7.132 Bathroom sockets: 30 mA RCD line or isolating transformer.

1.7.135 Combining N and PE in final circuits is prohibited.

Practical takeaways

Section 1.7 is the most cited part of PUE: TN-C-S choice, 30 mA RCDs, main and supplementary bonding, the N–PE prohibition (1.7.135). Harmonized with IEC 60364-4-41 and 5-54.