PUE section 1.2: reliability categories (1.2.17–1.2.21), special group of category 1, voltages.
| Document | PUE 7, Section 1.2 Power supply |
| Edition | 2002 (ПУЭ-7, разд. 1.2) |
| Status | Current |
| Issued by | Ministry of Energy of Russia |
| Applies to | Power supply and networks: reliability categories |
| № | Chapter / section |
|---|---|
| 1.2.1–1.2.16 | General supply requirements |
| 1.2.17–1.2.21 | Reliability categories |
| 1.2.22–1.2.33 | Voltages, network schemes |
1.2.17 Category 1: life-threatening consumers — two independent sources, interruption only for ATS time.
1.2.18 Special group: operating theatres, fire pumps, emergency lighting — three independent sources (2 intakes + DG/battery).
1.2.19 Category 2: two sources, interruption for manual transfer time.
1.2.20 Category 3: one source, repair-time interruption.
1.2.21 Residential buildings — no higher than category 2.
127/220/380 V single-phase; 220/380 V three-phase; new networks — 230/400 V.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.
← Back to the country: PUE Russia: Rules for Electrical Installations · World electrical installation rules