PUE 4.1: panels, busbars, walkways, earthing.
| Document | PUE 7, Chapter 4.1 LV switchgear |
| Edition | 2003 (ПУЭ-7, гл. 4.1) |
| Status | Current |
| Issued by | Ministry of Energy of Russia |
| Applies to | LV switchgear up to 1 kV: panels, busbars, walkways |
| № | Chapter / section |
|---|---|
| 4.1.1–4.1.8 | General |
| 4.1.9–4.1.18 | Busbars, apparatus |
| 4.1.19–4.1.25 | Walkways, maintenance, earthing |
Phase colors: L1 yellow, L2 green, L3 red; N blue; PE green-yellow.
≥ 0.8 m in front of panels (1 m double-sided); bare parts ≥ 2.2 m or guarded; enclosures and doors earthed (4.1.25).
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.