Top.Mail.Ru

PUE 7, Section 1.3 Conductor selection — clause by clause

PUE section 1.3: ampacity tables (1.3.4–1.3.7), economic current density, voltage drop check.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentPUE 7, Section 1.3 Conductor selection
Edition2002 (ПУЭ-7, разд. 1.3)
StatusCurrent
Issued byMinistry of Energy of Russia
Applies toConductor selection: heating, ampacity (tables 1.3.4–1.3.7), economic density

Document structure

№Chapter / section
1.3.1–1.3.9General, heating
1.3.10–1.3.21Ampacity tables
1.3.22–1.3.33Economic density, voltage drop
PUE 7, Section 1PUE 7, Section 7PUE 7, Chapter 2PUE 7, Chapter 3PUE 7, Section 1PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 1PUE 7, Section 6 LightingSP 256PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 2PUE 7, Chapter 4PUE 7, Chapter 7PUE 7, Chapter 7GOST R 50571 Building electrical installations (Russian IEC 60364)PUE 7, Chapter 2PUE 7, Chapter 7SP 158PUE 7, Chapters 2SP 76GOST R 50571Japan: electrical rules (JIS, 100 V)

General (1.3.1–1.3.9)

Conductors must satisfy heating limits: normal, emergency, post-emergency modes.

Ampacity (1.3.10–1.3.21)

3-core copper cable in conduit: 1.5 mm² — 14–19 A; 2.5 mm² — 21–27 A; 4 mm² — 28–38 A; 6 mm² — 36–46 A; 10 mm² — 50–70 A. Open — ~20–30% higher. Aluminium — ~25–30% lower. Ambient correction per table 1.3.3.

Economic density (1.3.22–1.3.33)

Copper 2.0–2.5 A/mm² (table 1.3.36); voltage drop check per 1.3.28.