Circuit breaker selection: complete guide

How to choose the rating, curve, and series of a circuit breaker. Current calculation, selectivity check, common mistakes.

Author: GorkyCAD Team

The circuit breaker — foundation of protection

The circuit breaker (MCB) is the basic element of any electrical installation. Safety of people and equipment depends on correct selection.

Step 1: Rated current

MCB rating In is selected by design current: In ≥ Icalc. For a kitchen outlet group (3.5 kW): Icalc = 3500 / 230 = 15.2 A → select C16.

Step 2: Trip curve (B, C, D)

B — 3-5 In (lighting, general outlets), C — 5-10 In (universal, outlets, small motors), D — 10-20 In (large motors, transformers, welders).

Step 3: Breaking capacity

Icu must exceed the maximum short-circuit current at the installation point. For apartment panels: 4.5-6 kA. For main switchboards: 10-15 kA.

Step 4: Selectivity

The upstream breaker must be rated at least 1.6× the downstream one for current selectivity.

Frequently asked questions