kVA to kW and kW to kVA

Convert apparent power (kVA) to active power (kW) and back: enter cos φ — for generators, transformers and UPS units.

Formulas

kW = kVA × cos φ; kVA = kW / cos φ.

Apparent power S (kVA) is what generators and transformers are rated in; active power P (kW) is what the consumer pays for. Reactive power Q = √(S²−P²) (kVAr) causes losses.

Typical cos φ values

Equipmentcos φ
Heaters, incandescent lamps1.0
Fluorescent lamps0.5–0.9
Induction motors0.7–0.9
Welding machines0.5–0.8
Computers, UPS0.6–0.9

Example

A 10 kVA generator at cos φ = 0.8 delivers 8 kW. Connecting a 9 kW load overloads it by current even at cos φ = 1 — size by kVA.

  • Generator sizing — generator
  • UPS sizing — ups
  • Power factor correction — power-factor

FAQ

What is the difference between kW and kVA?

kVA is apparent power (S), kW is active power (P). P = S×cosφ. The difference is reactive power, which does no useful work.

How many kW in 10 kVA?

At cos φ = 0.8: 10×0.8 = 8 kW. At cos φ = 1: 10 kW.

Why are generators rated in kVA?

Because generator current depends on apparent power: I = S/(√3·U). The active output depends on the consumer's cos φ.