--- Skip to content
Standards 2025-07-12 · 9 min

IEC 60364 vs PUE vs IS 732: comparing electrical standards

Comparative analysis of three standards systems: Russian PUE, international IEC 60364, and Indian IS 732. Key differences in calculations, terminology, and requirements.

Author: GorkyCAD Team

Introduction

An electrical designer working in Russia and India or with international projects encounters three standards systems:

  • PUE (Electrical Installation Code, 7th ed.) — Russia and CIS countries
  • IEC 60364 — international standard, basis for European norms
  • IS 732 (Indian Standard, adopted from IEC 60364) — India

Although IS 732 is based on IEC 60364, significant differences exist in practice. GorkyCAD supports calculations per all three systems — with automatic switching.

Comparison table

ParameterPUE (Russia)IEC 60364IS 732 (India)
Nominal voltage230/400 V ±10%230/400 V ±10%230/400 V (50 Hz)
Voltage drop limit5% from MDB3% (lighting), 5% (other)3% (lighting), 5% (other)
Cable sizing basisPUE tables 1.3.4-1.3.6IEC 60364-5-52IS 732, table 5
Iz 2.5 mm² Cu27 A (3-core, in chase)27 A (method C)27 A (method C)
Overcurrent protectionCh. 3.1IEC 60364-4-43IS 732 Section 4
RCD mandatoryCl. 7.1.71 (bathroom, sockets)IEC 60364-4-41IS 732 (≤20A sockets, wet areas)
EarthingTN-C-S, TN-STN, TT, ITTN-S (preferred)
SelectivityRecommendedIEC 60364-5-53IS 732 Section 5
Lightning protectionSeparate standardIEC 62305IS/IEC 62305 (adopted)
S/C current calcGOST 28249IEC 60909IS 13234 (based on IEC 60909)

Key calculation differences

Cable current ratings

For 2.5 mm² copper, 3-core:

  • PUE (in chase, brick): 27 A
  • IEC 60364 (method C): 27 A
  • IS 732 (method C): 27 A
→ Minimal differences here.

Voltage drop

  • PUE: single 5% limit for everything
  • IEC/IS: split — 3% lighting, 5% other

A lighting circuit at 4.5% passes PUE but fails IEC/IS (needs 3%).

RCD protection

  • PUE: mandatory for socket circuits, bathrooms. Type A recommended since 2020.
  • IS 732: mandatory for all ≤20A sockets in residential + all wet-area sockets. Type A recommended.
  • IEC 60364 (Germany): RCD ≤30 mA mandatory for all socket circuits ≤32 A.

→ IS 732 is generally stricter than PUE in coverage.

Earthing system

  • Russia: TN-C-S dominant (combined PEN at input, split at MDB). PUE permits.
  • India: de-facto standard — TN-S with separate N and PE throughout. IS 732 recommends TN-S for new installs.
  • IEC: recognizes all systems, TN-C-S has usage restrictions.

→ For Indian projects: PEN conductor not allowed after separation point. Always run separate N and PE.

Terminology differences

Russian (PUE)English (IEC)हिन्दी (IS 732)
Автоматический выключательCircuit Breaker (MCB)परिपथ विच्छेदक (MCB)
УЗОRCDअवशिष्ट धारा युक्ति (RCD)
ГРЩMain Distribution Board (MDB)मुख्य वितरण बोर्ड (MDB)
СечениеCross-Sectional Area (CSA)अनुप्रस्थ काट क्षेत्र (CSA)

How GorkyCAD simplifies work

  1. Country/standard selection at project creation — all norms auto-configured
  2. Standard switching for existing projects (e.g., started per PUE, client requested IS 732)
  3. Automatic recalculation on standard change
  4. Difference highlighting (where norms diverge)
  5. Trilingual BOMs (Russian/English/Hindi)

For engineers working on export or with Indian clients, this saves hours of manual recalculation and cross-checking.

Frequently asked questions

Is this article free?
Yes, all articles and calculators are completely free.
Where can I run calculations?
The site offers 21 free calculators: cable sizing, breakers, RCD, voltage drop and more.
How do I prepare an electrical project?
In GorkyCAD Pro: plans, panels, calculations and a PDF set for free.
Found an error in the article?
Write to hello@gorkycad.pro — specialists will review and correct it.

Open free calculators →

Related tools

Open free calculators →