--- Skip to content
Standards 2025-07-12 · 9 min

IEC 60364 vs PUE vs IS 732: comparing electrical standards

Comparative analysis of three standards systems: Russian PUE, international IEC 60364, and Indian IS 732. Key differences in calculations, terminology, and requirements.

Author: GorkyCAD Team

Introduction

An electrical designer working in Russia and India or with international projects encounters three standards systems:

- PUE (Electrical Installation Code, 7th ed.) — Russia and CIS countries

  • IEC 60364 — international standard, basis for European norms
  • IS 732 (Indian Standard, adopted from IEC 60364) — India

    Although IS 732 is based on IEC 60364, significant differences exist in practice. GorkyCAD supports calculations per all three systems — with automatic switching.

    Comparison table

    | Parameter | PUE (Russia) | IEC 60364 | IS 732 (India) |

|---|---|---|---| | Nominal voltage | 230/400 V ±10% | 230/400 V ±10% | 230/400 V (50 Hz) | | Voltage drop limit | 5% from MDB | 3% (lighting), 5% (other) | 3% (lighting), 5% (other) | | Cable sizing basis | PUE tables 1.3.4-1.3.6 | IEC 60364-5-52 | IS 732, table 5 | | Iz 2.5 mm² Cu | 27 A (3-core, in chase) | 27 A (method C) | 27 A (method C) | | Overcurrent protection | Ch. 3.1 | IEC 60364-4-43 | IS 732 Section 4 | | RCD mandatory | Cl. 7.1.71 (bathroom, sockets) | IEC 60364-4-41 | IS 732 (≤20A sockets, wet areas) | | Earthing | TN-C-S, TN-S | TN, TT, IT | TN-S (preferred) | | Selectivity | Recommended | IEC 60364-5-53 | IS 732 Section 5 | | Lightning protection | Separate standard | IEC 62305 | IS/IEC 62305 (adopted) | | S/C current calc | GOST 28249 | IEC 60909 | IS 13234 (based on IEC 60909) |

Key calculation differences

Cable current ratings

For 2.5 mm² copper, 3-core:

  • PUE (in chase, brick): 27 A
  • IEC 60364 (method C): 27 A
  • IS 732 (method C): 27 A
→ Minimal differences here.

Voltage drop

- PUE: single 5% limit for everything

  • IEC/IS: split — 3% lighting, 5% other

    A lighting circuit at 4.5% passes PUE but fails IEC/IS (needs 3%).

    RCD protection

    - PUE: mandatory for socket circuits, bathrooms. Type A recommended since 2020.

  • IS 732: mandatory for all ≤20A sockets in residential + all wet-area sockets. Type A recommended.
  • IEC 60364 (Germany): RCD ≤30 mA mandatory for all socket circuits ≤32 A.

    → IS 732 is generally stricter than PUE in coverage.

    Earthing system

    - Russia: TN-C-S dominant (combined PEN at input, split at MDB). PUE permits.

  • India: de-facto standard — TN-S with separate N and PE throughout. IS 732 recommends TN-S for new installs.
  • IEC: recognizes all systems, TN-C-S has usage restrictions.

    → For Indian projects: PEN conductor not allowed after separation point. Always run separate N and PE.

    Terminology differences

    | Russian (PUE) | English (IEC) | हिन्दी (IS 732) |

|---|---|---| | Автоматический выключатель | Circuit Breaker (MCB) | परिपथ विच्छेदक (MCB) | | УЗО | RCD | अवशिष्ट धारा युक्ति (RCD) | | ГРЩ | Main Distribution Board (MDB) | मुख्य वितरण बोर्ड (MDB) | | Сечение | Cross-Sectional Area (CSA) | अनुप्रस्थ काट क्षेत्र (CSA) |

How GorkyCAD simplifies work

1. Country/standard selection at project creation — all norms auto-configured

  • 2. Standard switching for existing projects (e.g., started per PUE, client requested IS 732)
  • 3. Automatic recalculation on standard change
  • 4. Difference highlighting (where norms diverge)
  • 5. Trilingual BOMs (Russian/English/Hindi)

    For engineers working on export or with Indian clients, this saves hours of manual recalculation and cross-checking.