--- Skip to content
Calculations 2025-07-01 · 10 min

Electrical safety calculations: S/C current, phase-neutral loop

Automating calculations in GorkyCAD. Single-phase S/C current, disconnection time check, phase-neutral loop.

Author: GorkyCAD Team

Why calculate the phase-neutral loop

The single-phase S/C current (phase-neutral loop) determines whether the MCB will trip within the required time (0.4 s for 220 V, IEC 60364). Insufficient S/C current → MCB won't trip in time → the enclosure stays live.

Formula

Isc(1) = Uph / (Ztr + Zw × L). Where: Uph = 220 V, Ztr — transformer impedance (typically 0.01-0.05 Ω), Zw — loop impedance per km for the cable (phase + neutral), L — line length.

Example

Outlet 30 m from panel, cable 3×2.5 mm² (copper). Zw = 14.8 Ω/km. Zline = 14.8 × 0.03 = 0.444 Ω. Zloop = 0.02 + 0.444 = 0.464 Ω. Isc(1) = 220 / 0.464 = 474 A. C16 MCB: 16 × 10 = 160 A (C upper limit). 474 > 160 — protection works.

Automation in GorkyCAD

GorkyCAD automatically calculates S/C currents for each line, checks compliance with MCB characteristics, and warns on non-compliance. Saves up to 50 manual calculations per project.

Frequently asked questions

Is this article free?
Yes, all articles and calculators are completely free.
Where can I run calculations?
The site offers 21 free calculators: cable sizing, breakers, RCD, voltage drop and more.
How do I prepare an electrical project?
In GorkyCAD Pro: plans, panels, calculations and a PDF set for free.
Found an error in the article?
Write to hello@gorkycad.pro — specialists will review and correct it.

Open free calculators →

Related tools

Open free calculators →