IEC 62305: LPL I–IV, rolling sphere radii, meshes, down conductors, SPDs, LPZ zones.
| Document | IEC 62305 Lightning protection (parts 1–4) |
| Edition | 2010 (части 1–4) |
| Status | Current (IEC 62305-1…4) |
| Issued by | IEC |
| Applies to | Lightning protection: LPL I–IV, risk assessment, LPS, SPDs |
| № | Chapter / section |
|---|---|
| Часть 1 | General principles, LPL |
| Часть 2 | Risk management |
| Часть 3 | Physical damage: LPS, meshes, down conductors |
| Часть 4 | Electronic systems: SPDs, LPZ |
Four levels: LPL I (99% interception) to LPL IV (91%), chosen by risk assessment.
Quantitative risk components vs tolerable values (10⁻⁵/year for life).
Rolling sphere: 20/30/45/60 m; meshes: 5×5/10×10/15×15/20×20 m; down conductors: 10/15/20/25 m for classes I–IV; roof metal ≥ 0.5 mm as natural terminal.
LPZ 0A/0B/1/2 zones; type 1 (10/350 µs) at the boundary, type 2 (8/20 µs) in main panels, type 3 near equipment.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.
← Back to the country: Europe: IEC 60364 and national codes (BS 7671, DIN VDE 0100, NF C 15-100) · World electrical installation rules