Clause-by-clause translation of IEC 60364-5-53: RCD installation (531), SPDs (534), isolation (536).
| Document | IEC 60364-5-53 Switchgear and surge protection |
| Edition | 2020 |
| Status | Current (IEC 60364-5-53:2020) |
| Issued by | IEC |
| Applies to | Switchgear, surge protection (SPD), RCDs, selectivity |
| № | Chapter / section |
|---|---|
| 530 | General |
| 531 | RCDs and their installation |
| 534 | SPDs — surge protection devices |
| 536 | Isolation, switching |
531.2 Type selection: AC / A / F / B by load; type A minimum for modern appliances.
531.3 RCDs for socket circuits (30 mA per 4-41), portable equipment, TT mandatory.
531.4 Fire-protection RCDs 300 mA at the intake (mandatory in some EU states).
534.4 Type 1 (10/350 µs) at the intake with lightning protection; type 2 (8/20 µs) in the main panel; type 3 near sensitive equipment. Coordination between stages.
536.1–536.3 Isolating devices at every intake; visible contacts; marked positions.