IEC 60364-4-43: overload (IB≤In≤Iz, I2≤1.45Iz), short-circuit protection, coordination.
| Document | IEC 60364-4-43 Overcurrent protection |
| Edition | 2015 |
| Status | Current (IEC 60364-4-43) |
| Issued by | IEC |
| Applies to | Overcurrent protection: overload and short circuit, coordination |
| № | Chapter / section |
|---|---|
| 431 | General |
| 433 | Overload protection |
| 434 | Short-circuit protection |
| 435 | Coordination |
433.1 IB ≤ In ≤ Iz and I2 ≤ 1.45 × Iz.
434.1 SC protection where fault current may exceed ampacity; 434.5.2 breaking capacity ≥ prospective fault current.
Combined devices (MCB) coordinate automatically; separate devices — verify characteristics.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.