Clause-by-clause translation of NEC Articles 300 and 310: NM cables and EMT, cable protection, burial depths, ampacity per Table 310.16, AWG to mm².
| Document | NEC 2023, Articles 300 (wiring) and 310 (conductors) |
| Edition | 2023 |
| Status | Current (latest NEC edition) |
| Issued by | NFPA |
| Applies to | Wiring methods (300) and conductors/ampacity (310) |
| № | Chapter / section |
|---|---|
| 300.1–300.25 | General wiring methods |
| 310.3–310.10 | Conductors: types, insulation |
| 310.12 | Dwelling service simplified sizing |
| Table 310.16 | Ampacity table (60/75/90 °C) |
300.4 Cable protection plates at wall/beam penetrations.
300.5 Burial depths: UF cables 0.45 m (18 in), conduits 0.15 m (6 in) with protection, under driveways 0.6 m (24 in); above-ground exits protected.
300.15 Splices only in accessible boxes.
310.3 Conductor types per environment: THHN, THWN-2, XHHW-2 (90 °C class).
310.12 Simplified dwelling sizing 120/240 V: up to 100 A — 4 AWG copper (2 AWG aluminium).
Copper at 75 °C, ≤ 3 conductors in conduit: 14 AWG — 20 A; 12 AWG — 25 A; 10 AWG — 35 A; 8 AWG — 50 A; 6 AWG — 65 A; 4 AWG — 85 A; 2 AWG — 115 A; 1/0 — 150 A. Correction factors: ambient, 4–6 conductors 0.8, 7–9 — 0.7.
12 AWG (3.31 mm²) — 25 A, close to 2.5 mm² per PUE (27 A). The difference: AWG sizes and 60/75/90 °C columns; dwellings use 75 °C.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.