NEC 2023, Article 210 Branch Circuits — translation

Clause-by-clause translation of NEC Article 210: GFCI in bathrooms/kitchens/outdoors, AFCI in dwellings, the 6-ft rule, kitchen countertop receptacle placement.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentNEC 2023, Article 210 Branch Circuits
Edition2023
StatusCurrent (latest NEC edition)
Issued byNFPA (National Fire Protection Association)
Applies toBranch circuits in dwellings and other occupancies: receptacles, GFCI, AFCI, receptacle placement

Document structure

№Chapter / section
210.1–210.7General
210.8GFCI protection
210.12AFCI protection
210.19–210.21Conductor sizes, ratings
210.50–210.63Receptacle placement
NEC 2023, Article 210 Branch CircuitsNEC 2023, Article 250 Grounding and BondingNEC 2023, Articles 300 (wiring) and 310 (conductors)NEC 2023, Article 230 ServicesNEC 2023, Article 240 Overcurrent ProtectionNEC 2023, Article 625 EV ChargingNEC 2023, Article 110 General requirementsNEC 2023, Article 220 Load calculationsNEC 2023, Article 517 Medical locationsNEC 2023, Article 500 Hazardous locations

General (210.1–210.7)

Article 210 covers branch circuits — from the last breaker to receptacles and appliances. Standard ratings: 15, 20, 30, 40, 50 A (210.3).

GFCI (210.8)

210.8(A) In dwellings, GFCI receptacles required: bathrooms, garages, outdoors, crawl spaces, unfinished basements, kitchen countertops, within 1.8 m of sinks, boat houses, bathtubs, laundry areas, indoor damp areas.

210.8(B) Non-dwellings: bathrooms, kitchens, sinks, outdoors, basements, wet areas.

210.8(F) Outdoor equipment (AC units, pumps) with accessible receptacles — GFCI too.

AFCI (210.12)

210.12 AFCI required in dwellings for circuits feeding bedrooms, living rooms, dining rooms, hallways, kitchens and most habitable rooms. AFCI detects arcing and disconnects before fire. Implemented as a breaker or the first receptacle.

Ratings (210.19–210.23)

210.19 20 A circuits — 12 AWG; 15 A — 14 AWG copper.

210.21 20 A circuits — 20 A receptacles (15 A allowed when multiple); 15 A circuits — 15 A only.

210.23 Continuous loads ≤ 80% of rating.

Receptacle placement (210.50–210.63)

210.52(A)(1) 6-ft rule: no point on a wall in a dwelling more than 1.8 m (6 ft) from a receptacle.

210.52(B)(1) Walls ≥ 0.6 m (2 ft) — at least one receptacle.

210.52(C) Countertops: no point more than 0.6 m (24 in) from a receptacle; islands ≥ 0.6 m — one each.

210.52(G) Bathroom: one 20 A GFCI receptacle within 0.9 m of the sink.

Practical takeaways

Article 210 is the inspector's first check: GFCI wherever water and outdoors, AFCI in habitable rooms, receptacles every 6 ft, countertops every 24 in. Unlike PUE (30 mA RCD in the panel), the US GFCI (4–6 mA) is often built into the receptacle.