NEC 2023, Article 250 Grounding and Bonding — translation

Clause-by-clause translation of NEC Article 250: system and equipment grounding, electrodes (2.44 m rods), Table 250.66 sizes, bonding.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentNEC 2023, Article 250 Grounding and Bonding
Edition2023
StatusCurrent (latest NEC edition)
Issued byNFPA
Applies toGrounding and bonding: electrodes, conductors, bonding

Document structure

№Chapter / section
250.1–250.10General, terms
250.30–250.36Separately derived systems
250.50–250.66Grounding electrodes
250.100–250.122Conductors, connections, sizes
NEC 2023, Article 210 Branch CircuitsNEC 2023, Article 250 Grounding and BondingNEC 2023, Articles 300 (wiring) and 310 (conductors)NEC 2023, Article 230 ServicesNEC 2023, Article 240 Overcurrent ProtectionNEC 2023, Article 625 EV ChargingNEC 2023, Article 110 General requirementsNEC 2023, Article 220 Load calculationsNEC 2023, Article 517 Medical locationsNEC 2023, Article 500 Hazardous locations

General (250.1–250.10)

Article 250 covers grounding of systems/equipment and bonding.

250.4 Effective fault current path, voltage limits on enclosures, neutral grounding.

250.6 Earth must not be the sole conductor.

System grounding (250.20–250.36)

250.24 Neutral grounded at the service; main bonding jumper only at the service (250.24(C)).

250.30 Separately derived systems (generators, transformers) — own electrode.

Electrodes (250.50–250.66)

250.50 All available electrodes bonded together.

250.52 Allowed: metal water pipe (first 1.5 m), rod 2.44 m (8 ft) long, ≥ 15.9 mm (5/8 in) copper-clad steel, plate, Ufer (rebar), cable sheath.

250.53 Rods below frost line; > 25 Ω — second rod.

250.66 Sizing table for grounding electrode conductor by phase size.

Conductors and bonding (250.100–250.122)

250.110–114 Equipment enclosures grounded; receptacles via earthing contact.

250.119 EGC green/green-yellow; neutral white/gray.

250.122 EGC table by breaker rating: 15 A — 14 AWG, 20 A — 12 AWG, 60 A — 10 AWG.

250.148 Bonding of boxes and receptacles.

Practical takeaways

Article 250 is the US equivalent of PUE 1.7: mandatory electrode list (2.44 m rod) instead of "4 Ω", sizing by tables 250.66/250.122, N-G jumper only at the service (like the PUE 1.7.135 prohibition).

Design with GorkyCAD Pro

Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.

Start free

Data is for reference. Final design decisions must follow current regulations and a qualified engineer.