PUE vs NEC: differences between Russian and US rules

PUE (Russia) vs NEC (US): 230/400 V vs 120/240 V, Schuko vs NEMA sockets, 30 mA RCD vs 4–6 mA GFCI, AWG vs mm² — key differences in tables.

PUE vs NECPUE vs IEC 60364PUE vs ChinaPUE vs IndiaNEC vs IECSockets and voltages worldwideRCDs worldwideChinaEuropePUE across CIS
🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Key differences

ParameterSide 1Side 2
Напряжение230/400 В, 50 Гц120/240 В, 60 Гц
РозеткиТип C / F (Schuko)NEMA 5-15R и др.
Сечения проводовмм² (1,5; 2,5; 4…)AWG (14, 12, 10…)
УЗО30 мА на группу в щитеGFCI 4–6 мА, часто в розетке + AFCI
ЗаземлениеTN-C-S; ≤ 4 Ом (1.7.51)TN-C-S; электроды 2,44 м (250.52)
Ванная комнатаУЗО 10 мА (7.1.81)GFCI (210.8), бритвенные розетки
Мин. сечение1,5 мм² медь14 AWG ≈ 2,08 мм²
ПроверкиПри приёмке (гл. 1.8)Инспекция при монтаже; периодичность — местно

Main differences in a table

Two independent traditions: Russian PUE (via the USSR) and US NEC (NFPA). Key differences: voltage and socket design, plus protection philosophy.

Voltage and sockets

Russia: 230/400 V, 50 Hz, Schuko (type F). US: 120/240 V, 60 Hz, NEMA 5-15R; 240 V between hot legs for heavy appliances.

RCD vs GFCI/AFCI

PUE: 30 mA RCD per circuit in the panel (7.1.79), 10 mA in bathrooms. NEC: GFCI at 4–6 mA, often in the receptacle (210.8); plus AFCI arc protection (210.12).

Sections: mm² vs AWG

Russia: 1.5/2.5/4/6 mm². US: 14/12/10 AWG (2.08/3.31/5.26 mm²). Same pairing logic: 2.5 mm² ≈ 12 AWG ≈ 16–20 A.

Earthing

Both TN-C-S. Russia: resistance ≤ 4 Ω (1.7.51). US: mandatory electrodes (2.44 m rod, 250.52) without a fixed ohm value.

Design with GorkyCAD Pro

Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.

Start free

Data is for reference. Final design decisions must follow current regulations and a qualified engineer.