Uninterruptible power supplies: offline/line-interactive/online types, power and runtime calculation, batteries, selection for boilers and computers.
| Type | Transfer | Output | Application |
|---|---|---|---|
| Offline | 4–10 ms | Mains + stepped sine | Computers |
| Line-interactive | 2–6 ms | Stabilized mains | Servers, boilers |
| Online (double conversion) | 0 ms | Pure sine, stabilized | Server rooms, medical, boilers |
P(VA) = P(W) / cos φ (0.6–0.7 for computers, 0.8 for boilers). Add 30–50% for inrush currents. Runtime: T = C×U×η/P with η ≈ 0.85.
| Task | Recommendation |
|---|---|
| Computer / router | Line-interactive 600–1500 VA |
| Gas boiler | Online 1–3 kVA pure sine + external batteries |
| Server / NAS | Online 1–3 kVA expandable |
| Whole house (short) | Online 5–10 kVA + generator/ATS |
Automatic single-line diagrams, IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.