btn btn-ghost btn-sm">Asboblar Marketpleys Sim o'tkazish narxi Usta topish Ustalar uchun ish Muharrirni ochish
Bosh sahifa

Voltage Drop Calculator

This calculator computes voltage drop in a cable line using the formula from IEC 60364 and GOST R 50571. All calculations are performed client-side — your data never leaves the browser.

How the calculation works

• For single-phase (230 V): ΔU = (2 × I × L × ρ × cos φ) / S
• For three-phase (400 V): ΔU = (√3 × I × L × ρ × cos φ) / S
• ρ (copper) = 0.0175 Ω·mm²/m, ρ (aluminum) = 0.028 Ω·mm²/m
• ΔU% = (ΔU / U_nom) × 100%
• Limits: < 3% — excellent, 3–5% — acceptable, > 5% — exceeded per IEC.

Kuchlanish pasayishi kalkulyatori

Kabel liniyasidagi kuchlanish pasayishini (ΔU) volt va foizda hisoblang: uzunlik, kesim, yuklama va cos φ hisobga olingan holda, bir fazali 230 V va uch fazali 400 V tarmoqlar uchun — GOST 32144-2013 normasiga muvofiqlikni tekshirish bilan.

Kalkulyator nimani hisoblaydi

O'tkazgich qarshiligida energiyaning bir qismi issiqlikka aylanadi va liniya oxirida kuchlanish kamayadi. Uzoq marshrutlarda (qishloq uylari, ishlab chiqarish maydonlari, yuqori qavatlarga ko'tarilishlar) pasayish sezilarli bo'ladi: lampalar xira yonadi, isitgichlar kamroq issiqlik beradi, motorlar quvvatini yo'qotadi.

Kalkulyator liniya parametrlari bo'yicha kuchlanish pasayishini volt va foizda hisoblaydi. Me'yor: yuklama tugunida kuchlanishning chetlashishi nominalning ±5% idan oshmasligi kerak (GOST 32144-2013), yoritish tarmoqlari uchun tavsiya etilgan pasayish 2,5%.

Hisoblash teskari masalani ham hal qiladi: berilgan uzunlik va yuklama uchun ruxsat etilgan pasayishni ta'minlaydigan maksimal liniya uzunligi yoki talab etiladigan kesim aniqlanadi.

Kalkulyatorning xususiyatlari

  • Bir fazali (230 V) va uch fazali (400 V) liniyalar uchun ΔU hisoblash
  • Yuklama toki yoki quvvati, cos φ ni hisobga olish
  • Natija volt va foizda (ΔU% = ΔU/U × 100)
  • Ruxsat etilgan pasayish bo'yicha maksimal uzunlikni aniqlash
  • Talab etiladigan kesimni hisoblash (pasayish sharti bilan)
  • Qarshilikni haroratga qarab tuzatish (ρ ≈ 0,0175 Om·mm²/m, mis)
  • GOST 32144-2013 normasi bilan taqqoslash

Hisoblash formulalari

Bir fazali liniya uchun (ikki o'tkazgich — boruvchi va qaytuvchi): ΔU ≈ 2 × I × L × ρ / S, bunda I — tok (A), L — liniya uzunligi (m), ρ — solishtirma qarshilik (mis uchun 0,0175 Om·mm²/m), S — kesim (mm²).

Uch fazali liniya uchun: ΔU ≈ √3 × I × L × (R × cos φ + X × sin φ), R — aktiv qarshilik, X — induktiv qarshilik (kichik kesimlarda X ni hisobga olmaslik mumkin, lekin 25 mm² dan yuqorida muhim).

Nisbiy pasayish: ΔU% = ΔU / U × 100. Maksimal ruxsat etilgan uzunlik: L_max = ΔU_ruxsat × S / (2 × I × ρ) — bir fazali liniya uchun.

Misol: 230 V tarmoqda, 2 kVt yuklamada (I ≈ 8,7 A), 20 m uzunlikda, 2,5 mm² kesimli mis liniya uchun ΔU ≈ 2 × 8,7 × 20 × 0,0175 / 2,5 ≈ 2,4 V ≈ 1,1% — me'yor doirasida.

ΔU ≈ 2·I·L·ρ/S (bir faza); ΔU ≈ √3·I·L·(R·cos φ + X·sin φ) (uch faza); ΔU% = ΔU/U × 100

Mis liniyada ΔU jadvali (230 V, 2 kVt, 20 m)

Kesim, mm²ΔU, VΔU, %
1,54,11,8
2,52,41,1
41,50,7
61,00,4

Me'yoriy baza

Kuchlanish sifati GOST 32144-2013 «Elektr energiyasi sifati me'yorlari» hujjati bilan tartibga solinadi; loyihalashda pasayishni hisoblash PUE (7.1-bob va 1.2-band) hamda СП 256.1325800.2016 talablariga muvofiq amalga oshiriladi. Asosiy me'yorlar:

— ta'minot markazidan eng uzoq iste'molchigacha bo'lgan liniyada ruxsat etilgan umumiy pasayish 5% dan oshmasligi kerak (turar joy binolari uchun);

— yoritish tarmoqlarida pasayishni 2,5% dan oshmaydigan darajada ushlab turish tavsiya etiladi;

— ikkala shart bajarilmasa, kesimni oshirish yoki yuklamani uch fazali liniyaga bo'lish kerak;

— 50 m dan ortiq liniyalar uchun kuchlanish pasayishini tekshirish majburiy.

Kalkulyatordan qanday foydalanish kerak

  1. Tarmoq turini tanlang: bir fazali 230 V yoki uch fazali 400 V.
  2. Liniya uzunligini metrlarda kiriting.
  3. Yuklama tokini (A) yoki quvvatni (kVt) va cos φ ni ko'rsating.
  4. Kabel kesimi va materialini tanlang.
  5. «Hisoblash» tugmasini bosing va ΔU ni volt/foizda, me'yor bilan taqqoslashni va tavsiyalarni oling.

Tez-tez uchraydigan xatolar

  • Uzoq marshrutlarda pasayishni tekshirmaslik — lampalar doim yarim quvvatda ishlaydi.
  • cos φ ni hisobga olmaslik — induktiv yuklamalarda (motor, yoritish) real pasayish kattaroq.
  • Bir fazali liniyada «2» koeffitsiyentini unutish — faqat bitta o'tkazgichning qarshiligi hisobga olinadi.
  • Faqat voltda baholash, foizda emas — 230 V va 400 V tarmoqlar uchun ruxsat etilgan foiz har xil.
  • Kesimni faqat qizish sharti bilan tanlash — uzoq liniyalarda hal qiluvchi omil pasayishdir.
  • Ko'tarilishlarni (qavatlarga) unutish — gorizontal marshrut qisqaroq.

Kuchlanish pasayishi haqida tez-tez beriladigan savollar

Ruxsat etilgan kuchlanish pasayishi qancha?

GOST 32144-2013 ga ko'ra yuklama tugunida kuchlanishning nominal qiymatdan chetlashishi ±10% dan oshmasligi kerak, lekin loyihalash amaliyotida qat'iyroq chegara qabul qilingan: ta'minot markazidan eng uzoq iste'molchigacha pasayish 5% dan oshmasligi, yoritish tarmoqlarida esa 2,5% tavsiya etiladi.

Kuchlanish pasayishi qachon eng muhim?

Uzoq liniyalarda (50 m dan ortiq) va katta toklarda. Tipik holatlar: qishloq uyiga yoki tashqi ob'ektga tortilgan havo liniyasi, uzun koridorlardagi yoritish, qozonxonada uzoqda joylashgan motor liniyalari. Qisqa xonadon liniyalarida (10–20 m) pasayish odatda 1% dan kam.

Kuchlanish pasayishini qanday kamaytirish mumkin?

To'rt yo'l bor: kabel kesimini oshirish (qarshilik kamayadi), marshrutni qisqartirish, yuklamani uch fazali liniyaga taqsimlash (pasayish √3 koeffitsiyenti bilan kamayadi) yoki yuqori kuchlanishli liniyaga o'tish. Amaliyotda eng osoni — kesimni bir pog'ona oshirish: masalan, 2,5 mm² o'rniga 4 mm².

Nega bir fazali liniya formulasida «2» koeffitsiyenti bor?

Chunki tok liniya bo'ylab ikkita o'tkazgichdan o'tadi: iste'molchiga boradi va manbaga qaytadi. Ikkala o'tkazgichda ham kuchlanish pasayadi, shuning uchun umumiy pasayish bitta o'tkazgich qarshiligidan ikki baravar ko'p. Uch fazali liniyada esa yuklama fazalar o'rtasida taqsimlanadi va koeffitsiyent √3 bo'ladi.

Kuchlanish pasayishi motorga ta'sir qiladimi?

Ha, sezilarli darajada. Motorning aylanish momenti kuchlanish kvadratiga proporsional: 10% pasayish momentni taxminan 19% kamaytiradi. Motor yuklangan holda ishlasa, tezligi pasayadi, toki oshadi va qiziydi. Shuning uchun motor liniyalari uchun pasayish 5% dan oshmasligi kerak.

🔌 Barcha vositalar