-lg text-text-primary group-hover:text-brand transition-colors">GorkyCAD Pro
Bosh sahifa
💡

Lighting Calculator

This calculator determines the required number of luminaires to achieve standard illuminance levels per EN 12464-1, IS 3646 and SP 52.13330. All calculations are performed client-side — your data never leaves the browser.

How the calculation works

1. The required illuminance (E, lx) is determined for the selected room type per EN 12464-1.
2. Total luminous flux: Φ = E × S / (UF × MF), where UF ≈ 0.5 (utilization factor), MF ≈ 0.8 (maintenance factor).
3. Number of luminaires: N = ⌈Φ / Φ_lamp⌉.
4. Specific power: P_spec = N × P_lamp / S.

Yoritish kalkulyatori

Xona uchun talab etiladigan yoritilishni (lyuks) hisoblang va lampalar sonini aniqlang: xona turi, maydoni, balandligi va lampaning yorug'lik oqimi hisobga olingan holda — SP 52.13330 me'yorlari asosida.

Kalkulyator nimani hisoblaydi

Yoritishni loyihalash xona turiga bog'liq bo'lgan me'yoriy yoritilish qiymatidan (E, lyuks) boshlanadi: turar joy xonasi uchun 150 lyuks, oshxona uchun 150, ofis uchun 300, yo'lak uchun 50 lyuks (SP 52.13330.2016).

Kalkulyator yorug'lik oqimi usulidan foydalanadi: talab etiladigan umumiy yorug'lik oqimi xona maydoni va me'yoriy yoritilishga proporsional bo'lib, bitta lampaning yorug'lik oqimi va xonaning aks ettirish xususiyatlariga bog'liq foydalanish koeffitsiyentiga bo'linadi.

Zamonaviy LED lampalar uchun ko'pchilik xonalarda yetarli qoida: har kvadrat metrga 3–4 Vt (turar joy xonalari uchun). Lekin aniq hisoblash uchun yorug'lik oqimi usuli majburiy — u xona balandligi, lampalarni osish balandligi va devor/ship rangini hisobga oladi.

Kalkulyatorning xususiyatlari

  • Xona turiga qarab me'yoriy yoritilishni aniqlash (SP 52.13330)
  • Lampalar sonini yorug'lik oqimi usuli bilan hisoblash
  • Xona indeksini hisoblash (i = A×B/(H×(A+B)))
  • Lampa turlarini tanlash: LED, lyuminestsent, cho'g'lanma
  • Zaxira koeffitsiyentini (Kz) va notekislik koeffitsiyentini hisobga olish
  • Solishtirma quvvat usuli bilan tez baholash
  • O'rtacha yoritilishni tekshirish hisobi

Hisoblash formulalari

Lampalar soni yorug'lik oqimi usuli bilan: N = E × S × K_z / (Φ_lampa × η × Z), bunda E — me'yoriy yoritilish (lyuks), S — xona maydoni (m²), K_z — zaxira koeffitsiyenti (LED uchun 1,15–1,3), Φ_lampa — bitta lampaning yorug'lik oqimi (lyumen), η — foydalanish koeffitsiyenti (0,3–0,7), Z — notekislik koeffitsiyenti (1,1–1,2).

Xona indeksi: i = A × B / (H_hisobiy × (A + B)), bunda A va B — xona o'lchamlari, H_hisobiy — lampadan ish sirtigacha balandlik. Indeks foydalanish koeffitsiyenti η ni aniqlash uchun ishlatiladi.

Solishtirma quvvat usuli: P = P_ud × S, bunda P_ud — solishtirma quvvat (LED uchun turar joy xonalarida 3–4 Vt/m²). Dastlabki baholash uchun ishlatiladi.

Misol: 20 m² turar joy xonasi, 150 lyuks, LED lampa 1000 lm: N = 150 × 20 × 1,2 / (1000 × 0,5 × 1,1) ≈ 6,5 → 7 lampa.

N = E·S·Kz/(Φ·η·Z); i = A·B/(H·(A+B)); P = P_ud·S

Yoritilish me'yorlari jadvali (SP 52.13330)

XonaE, lyuksSolishtirma quvvat, Vt/m² (LED)
Ofis / kabinet3006–8
Turar joy xonasi1503–4
Oshxona1503–4
Yotoqxona1002–3
Bolalar xonasi2004–5
Hammom501,5–2
Yo'lak / koridor501,5–2

Me'yoriy baza

Sun'iy yoritishni loyihalash SP 52.13330.2016 «Tabiiy va sun'iy yoritish» (yoritilish me'yorlari jadvallari), GOST R 55710-2013 «Ish joylarini yoritish me'yorlari» va PUE ning yoritish tarmoqlariga oid talablari bilan tartibga solinadi. Asosiy me'yorlar:

— turar joy binolarining asosiy xonalarida umumiy yoritilish kamida 150 lyuks bo'lishi kerak;

— ish sirtida (stol, oshxona stoli) yoritilish 300 lyuksgacha oshiriladi;

— yo'lak va yordamchi xonalarda 50–75 lyuks yetarli;

— lampalarning eskirishi va ifloslanishini hisobga olib zaxira koeffitsiyenti qo'llaniladi: LED uchun 1,15–1,3, lyuminestsent uchun 1,3–1,5.

Kalkulyatordan qanday foydalanish kerak

  1. Xona turini tanlang — kalkulyator me'yoriy yoritilishni avtomatik belgilaydi.
  2. Xonaning uzunligi, eni va balandligini metrlarda kiriting.
  3. Devor va ship rangini belgilang (foydalanish koeffitsiyenti uchun).
  4. Lampa turi va yorug'lik oqimini (lyumen) tanlang.
  5. «Hisoblash» tugmasini bosing va lampalar soni, umumiy quvvat hamda o'rtacha yoritilishni oling.

Tez-tez uchraydigan xatolar

  • Zaxira koeffitsiyentini hisobga olmaslik — bir necha yildan keyin yoritilish me'yordan pastga tushadi.
  • Osish balandligini noto'g'ri olish — foydalanish koeffitsiyenti o'zgaradi, hisob xato bo'ladi.
  • Devor va ship aks ettirishini hisobga olmaslik — to'q interyer qorong'i ko'rinadi.
  • Lyuks va lyumeni aralashtirish — lyuks sirt yoritilishi, lyumen lampaning yorug'lik oqimi.
  • Mahalliy yoritishni unutish — o'qish va ish zonalarida qo'shimcha yorug'lik kerak.
  • Lampalarni notekis joylashtirish — yoritish notekis bo'ladi, soyalar paydo bo'ladi.

Yoritish hisobi haqida tez-tez beriladigan savollar

Xona uchun necha lyuks kerak?

Xona turiga bog'liq: turar joy xonasi va oshxona uchun 150 lyuks, yotoqxona uchun 100, bolalar xonasi uchun 200, ofis uchun 300, yo'lak uchun 50 lyuks yetarli (SP 52.13330.2016). Ish sirtlarida (stol, oshxona stoli) yoritilish 300–500 lyuksgacha oshiriladi.

LED yoritish uchun har kvadrat metrga necha vatt kerak?

Turar joy xonalari uchun o'rtacha qiymat 3–4 Vt/m² (LED). Ya'ni 20 m² xona uchun umumiy quvvat 60–80 Vt yetarli — bu 6–8 lampa yoki 20 m² ga 3–4 Vt quvvatli osma lampa. Lekin aniq son lampaning yorug'lik oqimiga bog'liq: 1000 lyumenli 8 Vt LED lampa 60 Vt cho'g'lanma lampaga teng.

Nega yoritish hisoblanganidan xira bo'ladi?

Uch asosiy sabab: lampalarning eskirishi (yorug'lik oqimi yillar davomida kamayadi), ifloslanish (ship va lampalar ustidagi chang) va zaxira koeffitsiyentini hisobga olmaslik. Kalkulyator bu omillarni K_z = 1,15–1,3 koeffitsiyenti bilan hisobga oladi. Ikkinchi sabab: lampaning real yorug'lik oqimi qutidagidan kam — faqat taniqli brendlarni oling.

Eng yaxshi rang harorati qaysi?

Turar joy xonalari uchun 2700–3000 K (issiq oq) tavsiya etiladi — dam olish uchun qulay yorug'lik. Oshxona, hammom va ish zonalari uchun 3500–4500 K (neytral oq) mos keladi. Ofis va sinf xonalari uchun 4000–5000 K diqqatni oshiradi. 6000 K dan yuqori moviy yorug'lik uzoq ishlashda ko'zni charchatadi.

Yoritishni qanday teng taqsimlash mumkin?

Lampalarni xona bo'ylab bir xil joylashtiring: masalan, 20 m² xona uchun 7 lampa → 2 qator × 3–4 lampa. Markaziy osma lampa burchaklarni xira yoritadi — yoritishni zonali (osma, pol lampalari, LED lentalar) bilan to'ldirish yaxshiroq. Qoida: lampalar orasidagi masofa osish balandligining 1,5 baravaridan oshmasligi kerak.

🔌 Barcha vositalar