Short-Circuit Current Calculator

An engineering calculator for computing short-circuit currents in low-voltage 0.4 kV networks. Calculates steady-state three-phase short-circuit current, peak (making) current, and single-phase short-circuit current for protective device sensitivity verification.

Calculations follow GOST 28249-93 and IEC 60909 methodology. Parameters considered include supply transformer characteristics (power, short-circuit voltage), cable line impedance, contact transition resistances, and arc resistance.

Features

  • Three-phase short-circuit current calculation (Ik3)
  • Single-phase short-circuit current calculation (Ik1) — phase-to-neutral loop
  • Peak short-circuit current calculation (ip)
  • Transformer parameter consideration
  • Cable line impedance consideration (resistance + reactance)
  • Circuit breaker sensitivity verification
  • Comparison with device breaking capacity ratings

Standards

  • IEC 60909-0 — Short-circuit currents in three-phase AC systems
  • GOST 28249-93 — Short circuits in electrical installations up to 1 kV
  • PUE (Russia) — Electrical Installation Code

Frequently asked questions

What is the SC power at the input?

Sк — the short-circuit power at the service point (typically 6–20 MVA from a distribution transformer). Higher Sк means higher fault current.

Why check a 6 kA breaker?

The breaking capacity must not be lower than the fault current at that point. If the fault current exceeds 6 kA, use a 10 kA breaker.

Why does fault current drop along the line?

Cable resistance grows with length: R = ρ·2·L/S. At the end of a long run the fault current can be tens of times lower.

What fault current is in a socket outlet?

With Sк = 10 MVA and a 30 m run of 2.5 mm², the fault current ≈ 500 A — enough to trip the breaker and below 6 kA.

Courant de court-circuit

Calculez le courant de court-circuit à partir de la puissance de court-circuit du réseau.

Ce que ça calcule

  • Impédance du réseau : Z = U²/Sk
  • Résistance de la ligne : R = ρ·2·L/S
  • Courant de court-circuit en bout de ligne
  • Vérification du pouvoir de coupure

Normes

  • IEC 60947-2
  • IEC 60364-4-43

FAQ

Qu'est-ce que la puissance de court-circuit ?

La puissance de défaut au point de connexion (6–20 MVA typique).

Pourquoi vérifier 6 kA ?

Le pouvoir de coupure doit être ≥ au courant de défaut du point.